Home Electrical Testing
How to Test For What

Disclaimer
Electrical Testing in General
Interpreting 3-Prong Outlet Testers
Is a Device/Fixture Good?
Is There Hotness at a Device, Fixture, Box, or Wire?
Is There Neutral or Ground at a Device, Fixture, Box, or Wire?
Testing For Shorts and Ground-Faults

Home Electrical Testing in General

Review the various electrical testers here:

     ... Tester ...                ... Good For ...    ... Limitations ...    ... How To Use ... And review the logic behind using each. Shortly, I will suggest how to test various electrical devices and conditions. First, here are two things to note and some general testing principles.

One note is on testing for "hotness" and "neutralness." Most often when testers indicate the hotness or neutralness of a wire, this will also mean that the wire will be able to carry the current needed to run lights and appliances. Larry is advising this caller not to use a multimeterBut occasionally the wire will not sustain the needed voltage; contact is poor somewhere. Even 120 volts measured by a voltmeter may shrink down instantly when a real-life load tries to run. (The rest of this chapter will not generally take this condition or the next one into consideration.)

In addition, many testers may encounter a different condition, "phantom voltage." It will tend to register as 50 volts or less but might read almost as high as the usual voltage of the home (120 volts). It would not be able to shock you. It seems to be generated onto a wire that is neither hot nor neutral, by a hot wire that is bundled with it -- in the same cable, for instance. To be sure a reading is phantom, see that it will not run a light bulb, then that it does not spark when shorted to ground. Then ignore it.

This chart summarizes some electrical testing issues. It may help clarify your testing purpose:

 

PURPOSE
OF TEST
Points of contact Tester Notes
          A.
1. Shock hazard
2. Identity
3. For hotness, which might be able to carry load
1 Neon

Non-contact
Testers are looking for hotness. Identity includes which circuit (if hotness found) and (if not) extent of problem. This use of neon tester puts one probe in palm of hand (no danger with home voltage).
          B.
For voltage difference between points (both points might be able to carry load)
2 Neon

Volt

3-prong
These tests are relative and may need confirmation by A or C. 3-prong outlet tester reports three 2-point relations. Volt tester can be a multimeter.
          C.
For ability to carry load (to work)
2 Items of circuit

Bulb

Wiggins
These show functionality, not polarity or safety. If hot is identified by A, good ground or neutral is confirmed if this test works.
For outages, you might use the chart above generally as follows. After confirming with C that there is a problem, start with A and work your way from there to B to C again. If B indicates that something should now carry a load (work) but C shows that it will not, you can bring a known working non-GFCI hot and neutral via extension cord and perform the C test from it to the supposedly good neutral and hot (respectively), to see which is actually poor. Before doing so, be sure you will not be testing from hot to hot, since 240 volts might be involved and blow out your 120-volt test item (bulb).

Interpreting 3-Prong Outlet Testers (=3-hole/ receptacle testers)

The arrangement of the three lights on these receptacle testers is different among different manufacturers, but they all have one light to show a voltage difference between hot and neutral slots, another to show a voltage difference between the hot slot and the ground hole, and a third to show a voltage difference between the neutral slot and the ground hole. You could learn the same information by making three tests with the two probes of a neon tester or a voltage tester.

The three lights of a 3-hole outlet tester will light up for a range of voltages in the neighborhood of 120 volts, but sometimes a receptacle that is unable to run a lamp can run this 3-hole outlet tester; that is, under a real load the voltage does not remain as high as it tests. So an outlet that doesn't work might even read "correct wiring." Here are some more qualifications regarding outlet tester readings:

 

READING
QUALIFICATIONS
Correct wiring This is usually accurate. Occasionally the outlet still might not run normal items
Open hot (=no hot available) This reading can be false if neutral and ground are both poor -- a rare condition
Open ground (=no ground available) Such an actual condition will only give this reading if the neutral and hot are fairly good
Open neutral (=no neutral available) Such an actual condition will only give this reading if the ground and hot are fairly good
Reverse polarity = Hot and neutral reversed (=hot at left slot and neutral at right slot when viewed with ground-hole down) Such an actual condition will only give this reading if all three wires are fairly good. A hot ground could give this reading.
Hot and ground reversed Usually just a case of open neutral in which non-working but turned-on items in the outage allow hotness through them onto the white wires of the outage area. Polarity might be reversed too.
Hot on neutral with hot open Usually just a case of open neutral with reverse polarity

So the three-prong outlet tester can't always be taken at face value. There are other rare conditions that can give the same readings as these seven, and further testing, as outlined below, can discover these. Having said this, these outlet testers are handy and usually are telling the truth -- if you know how to interpret what they are saying. Learn more and see diagrams about the usual meaning of the six outlet tester readings at Outlet Corrections.

Your outlet tester may do double-duty as a GFCI outlet tester, simulating a ground-fault by the push of a button on it. There is a limitation here. Unlike a good GFI, which can test itself even without a good ground, the three-prong GFI outlet tester depends on a good ground to purposely trip the GFI; and this is also true when it is used to try tripping the GFI by pushing the tester's button at standard receptacles wired downstream from it.

Is a Device/Fixture Good?

Is a receptacle working? Best is to plug a good bulb or appliance in and see. A neon, receptacle, or volt tester may be handier, but they don't pull enough current to be sure the voltage is sustainable.
Is a light working? Screw in a bulb you know recently worked. A fluorescent fixture with more than one tube needs all brand-new tubes to test it reliably; also see this fluorescent troubleshooting site.
Is a switch working? If the switch is unable to turn on a good bulb, turn off the breaker, remove the wires from switch, connect those wires to each other, and turn the breaker on. If the item now works, the switch or its connections to the wires was probably bad.
Is a bulb good? Try it in a socket known to work. Otherwise test the removed incandescent bulb with ohmmeter: 4-200 ohms is a good bulb, but some good halogens indicate no continuity. Continuity testers vary and may not answer this question for bulbs of all wattages.
Is a fuse good? Best is to remove the fuse and test it with a continuity tester or ohmmeter; any substantial continuity means the fuse is good. If a round fuse is to be tested while in its fuseholder, slip one probe of a neon tester along side the fuse with the other to the palm of your hand. If it lights up, the fuse is good if this is a 120-volt circuit and if this fuse is for the hot, not the neutral; neutrals in some old homes were fused. For a cartridge-shape fuse that is accessible while in place, touch the probes of a neon tester to the ends of the fuse; if no light shows, the fuse is good, otherwise not -- assuming at least one end of fuse is hot -- so check that first.
Is a breaker good? If this question arises from losing power to the circuit, a short,overload, or open is more likely. If more things in the house work with the breaker on than off, the breaker is fine; you have an open. Be sure the breaker isn't simply tripped. Force it firmly into a full Off position, then firmly On. You could repeat this with the wire removed from the breaker, especially if the breaker didn't stay on or you heard a hum or buzz when you put it on. (These make it likely the breaker is fine and is responding to a short.) If you have the wire removed, you may as well do this test also: if the turned-on breaker's screw reads hot for a neon or volt tester, it is probably good. Also try to run a light bulb or Wiggins tester between that screw and a ground in the panel. The breaker is bad if these won't run. But the best all-around test is to move the breaker's wire temporarily to a new or different breaker, turning both off while moving it. With that breaker on, if the problem has gone away, figure the old breaker was bad; otherwise it is good. One more test would be to turn the breaker off, remove it, reset it to On, and check with an accurate ohmmeter between its screw and its bus-clip. It is likely bad if it reads more than 5 ohms.

Is There Hotness at a Device, Fixture, Box, or Wire?

Does hotness reach a certain receptacle or light? If your purpose in electrical testing is personal safety for working on your problem, a non-contact volt stick will alert you if there is some hotness present. (One exception is when you are checking an underground wire or cable you have uncovered.) When your purpose is to check the extent of a circuit or of an open hot, a neon tester will light up slightly for something hot. Have one of its probes in the palm of your hand. A non-contact voltage tester inserted in these same receptacle slots or light sockets will also indicate hotness. This does not tell you whether the outlet or light has a good neutral or ground.
Does hotness reach a certain electrical box or terminal? Having removed the cover, you can touch an in-hand neon or non-contact tester to the side-screw terminals of any switches or receptacles, but to check deeper in a box, the non-contact tester will be the easiest, once you loosen any devices in the way. At a circuit breaker one neon probe to the breaker's screw and the other in your palm will light it up if hotness is there. Don't trust a non-contact volt tester to help at a breaker since many nearby things are also hot. These tests do not tell you whether good neutrals or grounds are present.
Is a certain hot or neutral able to carry a load? Occasionally testers will show good voltage between hot and neutral, whereas plugging in a lamp or attaching a light socket and bulb to hot and neutral will show you that either the hot or the neutral is inadequate to run real things. Which one is poor? Unless you distrust the groundedness of the ground wire, connect a load (at least a light bulb worth) between it and the hot; if that runs the bulb, the neutral is poor; otherwise the hot is.
Which wire is hot? A neon tester with one lead in the palm of your hand is best. If it lights a bit when you touch it to the metal of a wire, at least that wire is hot, whether is it meant to be or not. A non-contact tester isn’t always able to be near one wire without also being near others. Also it too often reads a wire as hot which is merely not grounded and has gathered some "phantom" voltage from a hot wire it runs through the house with. An example would be an unhot traveler in a 3-way switch system.When a neutral is open somewhere on a circuit, white wires in the non-working area of the circuit can often read as hot -- and are somewhat -- in addition to the true hot. And of course, switched wires are hot when switched on and not when switched off. The fact that a wire is not hot does not mean it is always that way, nor that it is a neutral.
Is the voltage from hot to neutral too high or low? A voltmeter would be touched between hot and neutral. 120 volts, or 240 for special items, are nominal normal voltages supplied by the power company. The actual measured voltage at your home will be a little different -- as much as about 5% higher or lower. More variation than this is abnormal. It could be something the power company should correct, or it might indicate a neutral connection problem in one of your circuits or in your main wires.
Is a low but non-zero voltage reading significant? When a zero or 120-volt reading is expected but something in between is indicated by a voltmeter (5-100 volts), this may mean a connection is poor. However, it could be due to phantom voltage; such voltage, when shorted to ground, gives no spark and should be ignored.

Is There Neutral or Ground at a Device, Fixture, Box, or Wire?

Does "neutralness" reach a certain receptacle or light? If you trust the hot there, plugging in a lamp or screwing in a good bulb shows whether the neutral is good. If the hot is questionable, bring a good hot via an extension cord to where you can attach both it and the neutral in question, to the wires of a socket to run a bulb. A less reliable indication that a neutral is healthy is if a continuity tester or ohmmeter shows continuity between it and the ground wire; this should be done with the breaker off.
Does neutral reach a certain electrical box? Approach this as stated for the previous question. However, the neutrals at switch boxes are often less accessible for contacting or attaching to. In such cases, wire connectors may have to be undone to test. The breaker of the circuit(s!) involved in the box should be off until everything is ready for the testing. If neutrals are separated in order to test, it is normal, if you think about it, for only one of these whites to then test out as the neutral.
Is a ground wire good? If a light socket and bulb attached from hot to neutral works and works attached from hot to ground, the ground is good; if it works from hot to neutral but not from hot to ground, the ground is bad. An outlet, neon, or volt tester may indicate some groundedness, but these do not tell you for sure that a ground is solid. For what to do about a bad or missing ground, you might want to refer to my discussion of Home inspection findings.

Electrical Testing For Shorts And Ground-Faults:

Is a hot-to-neutral short present? The breaker itself -- tripping off -- is the best test of the shorting. If the circuit uses a fuse, don't repeatedly replace it to test the short unless you use a main pull-out or disconnect ahead of it to recontact the short. The arcing of a short would do damage to a round fuse's holder. The matter of whether it is the neutral that the hot is shorting to can be determined by disconnecting that circuit's neutral from the panel's neutral bar, capping it, and seeing that the short is then gone. An ammeter clamped on the hot wire at the breaker or fuse can also confirm that it is tripping/blowing for high current. Clamped on the circuit's neutral, it would also show that the short is indeed running hot-to-neutral. An ohmmeter showing 0-5 ohms between suspected wires will tend to mean the short is still there, but since lightbulbs and motors out on the circuit could give such a low resistance reading, I recommend against giving such a test much weight. Give a continuity tester even less weight for the same reason.
Is a hot-to-ground short present? If a breaker or fuse has been tripping/blowing, it will be the best indicator, and a procedure corresponding to that mentioned above regarding the hot-to-neutral short, will apply. But if the short is only tripping a GFCI receptacle, that is the best indicator.
Is a neutral-to-ground fault present? No regular breaker will trip for this. A GFI receptacle or GFI breaker will, and is the best way to keep testing. If an ohmmeter showed up to 30,000 ohms from the ground to load white(s), (disconnected from the line white), this might mean the fault is present.
Is this receptacle dead from a tripped GFI receptacle somewhere? A GFI receptacle disconnects both hots and neutrals when it trips. So an ohmmeter or continuity check between the neutral slot and the ground hole of a totally dead regular-looking receptacle will tell whether a tripped GFI is likely. Normally a dead receptacle with no hotness retains continuity between neutral and ground (assuming the ground is good), since both are connected to the neutral bar in the panel. But one that is downstream from a tripped GFI should show no continuity. See Is a GFI to blame?

HOW TO CONTACT Detective Larry
HOME of The Circuit Detective

© 2007 Larry Dimock